Categories: Novice electricians, Industrial electrician
Number of views: 14968
Comments on the article: 4

What determines the long-term permissible cable current

 

What determines the long-term permissible cable current? To answer this question, we will have to consider transient thermal processes that occur under conditions when an electric current flows through the conductor. Heating and cooling a conductor, its temperature, connection with resistance and cross-section - all this will be the subject of this article.


Transition process

What determines the long-term permissible cable current

To begin with, consider a conventional cylindrical conductor of length L, diameter d, cross-sectional area F, resistance R, volume V, obviously equal to F * L, through which current I flows, the specific heat of the metal of which the conductor is made - C, the mass of the conductor is equal to

m = V * Ω,

where Ω is the density of the metal of the conductor, S = pi * d * L is the area of ​​the side wall through which cooling occurs, Tpr is the current temperature of the conductor, T0 is the ambient temperature, and, accordingly, T = Tpr - T0 is the temperature change. KTP is the heat transfer coefficient, numerically characterizing the amount of heat transferred from a unit surface of a conductor in 1 second at a temperature difference of 1 degree.

Graphs of current and temperature in the conductor over time

The figure shows graphs of the current and temperature in the conductor over time. From time t1 to time t3, current I flowed through the conductor.

Here you can see how, after turning on the current, the temperature of the conductor gradually rises, and at time t2 it ceases to increase, stabilizes. But after turning off the current at time t3, the temperature begins to gradually decrease, and at time t4 it again becomes equal to the initial value (T0).

So, it is possible to write down the heat balance equation, a differential equation for the heating process of the conductor, where it will be reflected that the heat released on the conductor is partially absorbed by the conductor itself, and partially is given to the environment. Here is the equation:

On the left side of equation (1) is the amount of heat released in the conductor during the time dt, the passage of current I.

The first term on the right side of equation (2) is the amount of heat absorbed by the conductor material, from which the conductor temperature increased by dT degrees.

The second term in the right-hand side of equation (3) is the amount of heat that was transferred from the conductor to the environment during the time dt, and it is related to the surface area of ​​the conductor S and the temperature difference T through the thermal conductivity coefficient Ktp.

First, when the current is turned on, all the heat released in the conductor is used to heat the conductor directly, which leads to an increase in its temperature, and this is due to the heat capacity C of the conductor material.

With increasing temperature, the temperature difference T between the conductor itself and the environment increases accordingly, and the heat generated partially goes already to increase the ambient temperature.

When the temperature of the conductor reaches a steady stable value of Tust, at this moment all the heat released from the surface of the conductor is transferred to the environment, so the temperature of the conductor no longer increases.

The solution to the differential heat balance equation will be:

In practice, this transient process lasts no more than three time constants (3 * τ), and after this time the temperature reaches 0.95 * Tust. When the heating transition process stops, the heat balance equation is simplified, and the steady-state temperature can be easily expressed:


Permissible current

Now we can come to the exact value of the current that appears to be a long-term allowable current for a conductor or cable. Obviously, for each conductor or cable there is a certain normal continuous temperature, according to its documentation.This is such a temperature at which a cable or wire can be continuously and for a long time without harm to itself and to others.


From the above equation it becomes clear that a specific current value is associated with such a temperature. This current is called permissible cable current. This is such a current, which, when passing through the conductor for a long time (more than three time constants), heats it to an allowable, that is, normal temperature Tdd.

Here: Idd - long-term allowable conductor current; TDD - permissible conductor temperature.

To solve practical problems, it is most convenient to determine the long-term allowable current according to special tables from the PUE.

Type of conductor
Permissible temperature
Short-term allowable temperature
Bare conductor or bus
70aboutFROM
Copper - 300aboutFROM
Bare conductor or bus
70aboutFROM
Aluminum - 200aboutFROM
Cable in paper insulation up to 3 kV
80aboutFROM
200aboutFROM
Cable in paper insulation up to 6 kV
65aboutFROM
200aboutFROM
Cable in paper insulation up to 10 kV
60aboutFROM
200aboutFROM
Cable in paper insulation up to 35 kV
50aboutFROM
125aboutFROM
Cable in rubber insulation up to 1 kV
65aboutFROM
150aboutFROM
Cable in PVC insulation up to 1 kV
65aboutFROM
150aboutFROM
XLPE insulated cable up to 1 kV
90aboutFROM
250aboutFROM

In the event of a short circuit, a significant short circuit current flows through the conductor, which can significantly heat the conductor, exceeding its normal temperature. For this reason, conductors are characterized by a minimum cross-section based on the condition of short-term heating of the conductor by a short circuit current:

Here: Ik - short circuit current in amperes; tp is the reduced short-circuit current duration in seconds; C is a coefficient that depends on the material and construction of the conductor, and on the short-term allowable temperature.

Electric cable in the store

Section Connection

Now let's see how the long-term allowable current depends on the cross section of the conductor. Having expressed the area of ​​the side wall through the diameter of the conductor (the formula at the beginning of the article), assuming that the resistance is related to the cross-sectional area and the specific resistance of the material of the conductor, and substituting the well-known formula for resistance into the formula for Idd, given above, we obtain for a long-term allowable current Idd formula :

It is easy to see that the connection between the long-term admissible current of the conductor Idd and the cross-section F is not directly proportional, here the cross-sectional area is raised to the power ¾, which means that the long-term permissible current increases more slowly than the cross-section of the conductor. Other constants, such as resistivity, heat transfer coefficient, permissible temperature, are individual by definition for each conductor.

In fact, it is, the dependence cannot be direct, because the larger the cross section of the conductor, the worse the cooling conditions of the inner layers of the conductor, the more acceptable temperature is reached at a lower current density.

If you use conductors of larger cross section to avoid overheating, this will lead to an excessive consumption of material. It is much more profitable to use several conductors of small cross section laid in parallel, that is, use multicore conductors or cables. And the relationship between the long-term allowable current and the cross-sectional area as a whole turns out like this:

F
1
2
4
Idd
1
1,68
2,83

Current and temperature

To calculate the temperature of a conductor with a known current and specified external conditions, consider the steady state when the temperature of the conductor reaches Tust and no longer increases. Initial data - current I, heat transfer coefficient Ktp, resistance R, side wall area S, ambient temperature T0:

A similar calculation for continuous current:

Here, T0 is taken as the calculated ambient temperature, for example + 15 ° C for laying under water and in the ground, or + 25 ° C for laying in the open air. The results of such calculations are given in tables of continuous currents, and for air they take a temperature of + 25 ° C, because this is the average temperature of the hottest month.

Dividing the first equation by the second, and expressing the temperature of the conductor, we can obtain a formula for finding the temperature of the conductor at a current other than the long-term allowable, and at a given ambient temperature, if a long-term allowable current and a long-term allowable temperature are known, and you do not need to resort to using other constants:

From this formula it is seen that the temperature rise is proportional to the square of the current, and if the current increases by 2 times, then the temperature increase will increase by 4 times.

Electric cable in the electrical panel

If external conditions differ from the design

Depending on the actual external conditions, which may differ from the calculated ones depending on the method of laying, for example, several conductors (cable) located in parallel or laying in the ground at a different temperature, an adjustment of the maximum permissible current is required.

Then, the correction factor Kt is introduced, by which the long-term allowable current is multiplied under known (tabular) conditions. If the external temperature is lower than the calculated one, then the coefficient is greater than one; if it is higher than the calculated one, then, accordingly, Kt is less than one.

When laying several parallel conductors very close to each other, they will additionally heat each other, but only if the surrounding environment is stationary. Actual conditions often lead to the fact that the environment is mobile (air, water), and convection leads to cooling of the conductors.

If the medium is almost stationary, for example, when laying in a pipe underground or in a duct, then mutual heating will cause a decrease in the long-term allowable current, and here you need to enter the correction factor Kn again, which is given in the documentation for cables and wires.

See also at bgv.electricianexp.com:

  • Thermal action of current, current density and their influence on the heating of conductors
  • How to calculate the filament temperature of a filament lamp in nominal mode
  • How to find out how much power a cable or wire can withstand
  • Copper or aluminum - which is more profitable?
  • How to choose a cable section - designer tips

  •  
     
    Comments:

    # 1 wrote: | [quote]

     
     

    In general, every self-respecting supplier of wires or cables provides today accompanying tables, where for a particular wire in various conditions you can easily find a long-term allowable current, and not be mistaken. The manufacturer himself makes all the necessary calculations and calculations, and the consumer can only choose from the table a cable or wire of suitable section and the required modification.

     
    Comments:

    # 2 wrote: Anatoly | [quote]

     
     

    That's right! But not only when laying the cable in the ground, but also when laying it directly in the gates under the plaster, the conditions for laying the cable may differ from the calculated ones (unfortunately, in the regulatory and technical documents, including the PUE, this issue is not given due attention), hence the errors when laying the cable. For example, according to the PUE, the nominal current of the cable when laying it in the pipe, and the PVC corrugation is essentially a flexible PVC pipe, the nominal current of the cable, with a coefficient of fill of the corrugation with a cable of 0.3 - 0.5, is 21 amperes, and in the sand - cement plaster - 20 amperes. If you use GOST RM EK 60287 - 2 - 1 - 2009, then, knowing that the thermal resistance of sand-cement plaster, on average, is 1 (m * degree Celsius / Watt), and the thermal resistance of the lung of aerated concrete is equal to 10 (m * degree Celsius / Watt), we obtain that the rated current of the cable current in aerated concrete is 20 * 20/10 = 40, we extract the square root and get about 7.1 amperes, operating practice has shown that in real laying conditions, when one side is covered with gypsum, the rated current of the cable is about 10 amperes, twice and less than in sand and cement plaster. The same applies to other building materials. If the cable stretches across an extended section of aerated concrete, gypsum, etc., according to the PUE, the rated current of the cable must be selected according to the worst conditions for laying it or current at 10 amperes and a 6 amp amp cayuel circuit breaker. BUT, if you lay the cable, and also the wire, so that the sheath does not prevent it from cooling better, then the nominal current of the cable is 21 amperes, since the environment of its laying has not changed.And the operating practice confirms that this is so. Thus, the most important purpose of a corrugation is to preserve the rated current of the cable regardless of the conditions of its laying, that is, regardless of the thermal resistance of the materials on which the cable is laid. The corrugation is specially designed to meet this requirement preserving the rated current of the cable, the thermal energy released by the cable is absorbed by the air in the corrugation and the material of the corrugation itself by convection and heat radiation, and heat transfer does not play a significant role the role of cooling the cable, due to the very large thermal resistance of the air and the corrugation itself, of course, when laying on materials with low thermal resistance, the temperature of the corrugation decreases and it is able to absorb more thermal energy, but this reduction is not significant. Even when laying the cable in the corrugation in aerated concrete , the thermal resistance of aerated concrete is not more than 18 - 20% of the thermal resistance of air in the corrugation. That is, even with an infinitely large resistance of the external environment of laying the corrugation, the cable at rated current is not heated The temperature will be higher than the permissible temperature, and in an environment with low thermal resistance, the cable will have a temperature when laying it in the corrugation even lower than the maximum allowable. The corrugation was created instead of steel pipes, when various materials with different thermal resistance along the cable laying routes began to be used in construction .

     
    Comments:

    # 3 wrote: Nikolay | [quote]

     
     

    Any continuously flowing current under constant external conditions corresponds to a well-defined steady-state temperature of the conductor. The magnitude of the long-running current at which the temperature becomes the maximum allowable for a given brand of wire or cable is called the long-term allowable current load.

    The magnitude of the long-term permissible current depends on the material and cross-section of the conductor, the ambient temperature, the insulation material and the laying method. The mode of operation of wires and cables also matters. In intermittent operation, the permissible current load can be increased. To determine the value of the long-term allowable current, it is important to know the highest positive ambient temperature, since at low temperatures at the same current more favorable working conditions of wires and cables are provided.

     
    Comments:

    # 4 wrote: Alex | [quote]

     
     

    It is not clear - as for a wire with a square cross section of 2 mm, the current strength is only 1.68 A ???

    25A you can lightly, I don’t understand anything ...